AVANT KE – KG
Description: AISI 304 (KE) or AISI 316L (KG) stainless steel inner wall and AISI 304 stainless steel outer wall. Rock wool: density 128 kg/m³, thickness 25 mm. Absense of thermal brigde, ring-free connection system. For the instalation of the product you must use a sealant in accordance to CONVESA instructions.
Utilities: For boilers or engines in positive pressure (up to 5000 Pa) that work in dry conditions or wet conditions (condensation) and use gas, gasoil or solids (firewood, coal pellets, etc) as fuel
Assembly:
Interior and exterior
Designation: · KE: EN 1856-1 T600-H2-W-Vm-L20040/050/060-O (60).
· KG: EN 1856-1 T600-H2-W-Vm-L50040/050/060-O (60).

Distance to combustible materials:
Ø80 a Ø300 = 60 mm;
Ø350 a Ø450 = 90 mm;
Ø500 a Ø600 = 120 mm;
Ø650 a Ø800 = 240 mm.